¢º
Calculate required output torque (T1) or Power (kW)
Refer to Convenient Formula
for the relations among the Torque(T1),Power
(kW) and Horse Power(HP).
¢º Calculate
required output shaft speed(n2) and input shaft speed
(n1) or transmission ratio Refer
to Convenient Formula
for the relations among the Output Speed ,Input
Speed and Reduction ratio
¢ºDetermine the
service factor Refer
to the CH 4-1) Load
Classification and Service Factor (Sf) CH 4-2) Service factor for selection
¢ºSelect the
proper reducer size on the basis of power rating Pin greater than or equal to P2
X Sf
Refer
to CH 7-1.Nominal
Power Rating
where |
Pin= nominal power rating P2 =
required power rating Sf=service factor |
¢º Check
Thermal capacity It is
important to check whether thermal capacity rating
PT1
exceed calculated
power rating value. .If Thermal Capacities are less
than Power Rating value , you have to consider
the auxiliary cooling system or select more larger reducer
size. Refer to CH.7-2.Thermal
Capacity
where |
PT= thermal capacity Pin =
nominal power rating |
¢ºVerify permissible over hung load
by referring to the instructions and values specified
on Over Hung Load
If the over hung load is greater than
that of allowable value ,select the next larger frame
size or use third bearings with an extended shaft. You
have to consider that over loads are caused by low transmission
ratio, high force of interia, braking, higher power
than required and other dynamic and static loads.
If you have any questions or severe operating conditions,
consult us. |